ElectricalDemandFactorRule

Description:
This enum describes the different demand factor rule types available to the application. Within a demand factor a rule will be referenced and the user will have to enter values corresponding to that rule.
Name Description
E Constant This rule will apply a constant demand factor to the loads, regardless of values. It will also be the default for any newly created demand factor, and the default used if a demand factor cannot be found for a load classification.
E LoadTable This rule will apply the demand factor for the total load of attached objects to a panel. It is purely a look-up table. For example, if there are 5000 kVA, the user can specify 125% value is applied. If there are 20,000 kVA, the user can specify 100% value is applied.
E LoadTablePerPortion This rule will apply the demand factor differently for each row in the table. For example, the 3000kVA will have a 100% demand factor applied, the next 9000 will have a 35% factor applied, and the remaining items will have a 25% factor applied.
E QuantityTable This rule will apply the demand factor for the total quantity of attached objects to a panel. It is purely a look-up table. For example, the user can specify that 0 to 2 objects get 100% and 2 to 4 objects get 85% and so on.
E QuantityTablePerPortion This rule will apply the demand factor differently for each row in the table. For example, the first two (largest) items will have a 125% demand factor applied and the remaining items will have a 75% factor applied.